Disapproval Remarks


Process Number:  C2017072376 Review Type:  STRU  STRUCTURAL

Disapproval Remarks
-- ENTERED 03/08/2017 RESCAL -- APPROVED 02/15/2018 E319929
A - *** 3/7/2017 RE
A - 1)- PROVIDE S & S SPECIAL INSPECTOR FORM FOR:
A - SOIL COMPACTION (CMDC, SECTION 8-22),
A - REINFORCED MASONRY (FBC 2122.2.4 & CMDC, SECTION 8-22.),
A - 2)- S-1: PROVIDE DIMENSION TO LOCATE FOOTING F-5, F-6 ON FRAMING PLAN.
A - 3)- S-1: VERIFY FOOTING F-5SHORT WAY BARS TO COMPLY WITH FLEXURAL MINIMUM
A - REINFORCEMENT. ACI-318-11, SECT. 10.5.4
A - 4)- S-2: PROVIDE PUNCHING SHEAR CHECKING FOR COLUMN C7.
A - 5)- S-2: CLARIFY LOW ROOF SLAB WITH 180 HOOKS INDICATED AT UPPER SIDE OF THE
A - DRAWING OF THE SLAB.