Disapproval Remarks


Process Number:  C2017072376 Review Type:  STRU  STRUCTURAL

Disapproval Remarks
-- ENTERED 03/08/2017 RESCAL -- APPROVED 02/15/2018 E319929
A - 5)- S-5: STEP DOWN AT ROOF: VERIFY DETAIL SHOWING REINFORCEMENT LAYOUT AND
A - HORIZONTAL DIMENSIONS OF THE STEP, TO PROVIDE ADEQUATE REINFORCEMENT
A - CONTINUITY.
A - 5)- MISSING CALCULATION FOR FOOTING F-3. VERIFY FOOTING THICKNESS VS 1/S-1.
A - NOTICE THAT THE PROVIDED DETAIL SHOW A REDUCTION OF 4 INCHES. PROVIDE
A - CALCULATIONS.
A - 6)- S-4: STAIR REINFORCEMENT APPEARS TO BE INCOMPLETE. PLEASE CLARIFY.
A - 7)- S-4: VERIFY COLUMN C4 AND C5 REINFORCEMENT. AREA OF LONGITUDINAL
A - REINFORCEMENT FOR COMPRESSION MEMBERS SHALL NOT BE LESS THAN 0.01 AG. ACI 318
A - SEC. 10.9.1.